ABB R low-voltage reactors are used with capacitors in documented detuned power-factor correction arrangements. Identify the full reactor reference and coordinated capacitor-bank duty using the original table and applicable ABB catalogue before selecting or requesting a quote.

ABB R Low-Voltage Reactors

Key Features

Detuned compensation duty

ABB’s power-quality catalogue identifies R low-voltage reactors for series connection with power-factor correction capacitors. The documented role includes limiting switching inrush and reducing harmful harmonic amplification/resonance in a correctly designed capacitor installation. They are not generic line reactors for every drive application.

The original 18 references include R7% and R14% descriptions and single-phase/three-phase arrangements. In the cited catalogue, the percentage denotes the reactor-to-capacitor fundamental-frequency impedance ratio, rather than an efficiency or current rating. Select the complete capacitor/reactor combination from the applicable documentation.

Capacitor and reactor selection

Net bank output and the capacitor unit’s nameplate kvar are different quantities. The capacitor voltage rating in a detuned circuit also needs verification. A reactor should not be chosen simply by matching a kvar number or assuming one detuning percentage suits every harmonic spectrum.

  • Provide network voltage, frequency, phase arrangement and compensation step/net output requirement.
  • Provide harmonic measurements and nonlinear-load information for the system design.
  • Confirm detuning requirement, capacitor voltage/kvar, reactor current/inductance and the coordinated combination.
  • Check losses, ambient temperature, ventilation, thermal protection, terminals and mounting clearances for the exact unit.

Historical references and quotation

The existing model and Vendor Code data are retained. The 2015 ABB catalogue is a technical reference, not proof of current availability or status. Other names in the existing overview should be verified against complete ABB documentation before ordering; no unverified rating or replacement relationship is assigned to them.

Send the full reference and code, nameplate photos, quantity and destination, network conditions, capacitor-bank details and requested detuning. Product status and current availability should be confirmed before ordering.

Browse Power Quality, CLMD capacitor references or Contact. Official basis: ABB Power Quality catalogue 1SXF320002C2001, section 3. The original download below is retained.

Popular Models

R7
R14
R20
R25
R40
R50

Complete Model List

Model Vendor Code
R7% 15KVAR 400V 50Hz10117956
R7% 25KVAR 400V 50Hz10117957
R7% 30KVAR 400V 50Hz10117958
R7% 45KVAR 400V 50Hz10117959
R7% 50KVAR 400V 50Hz—
R14% 15KVAR 400V 50Hz—
R14% 25KVAR 400V 50Hz10180423
R14% 30KVAR 400V 50Hz10117954
R14% 45KVAR 400V 50Hz10117955
R14% 50KVAR 400V 50Hz10180424
R7% 5KVAR 400V 50Hz(1PH)10182601
R7% 10KVAR 400V 50Hz(1PH)10167085
R7% 15KVAR 400V 50Hz(1PH)10182603
R14% 5KVAR 400V 50Hz(1PH)10182602
R14% 10KVAR 400V 50Hz(1PH)—
R14% 15KVAR 400V 50Hz(1PH)10182604
R7% 15KVAR 400V 50Hz(1PH)(DE)10174342
R14% 25KVAR 400V 50Hz(Copper)10255249

Downloads

Request a Quote

Request a Quote